The 36kV Drop Out Fuse Cutout is designed for overhead power distribution systems to provide reliable protection against overload and short circuit conditions. It is widely used in electrical utility networks, substations, and transmission line applications.
Manufactured with high-quality insulating materials and durable galvanized metal components, the fuse cutout offers excellent electrical insulation performance, weather resistance, and long service life in outdoor environments.
Reacon provides professional power distribution protection equipment and overhead line hardware solutions for global utility projects.

For polymer insulator, the hardware fitting crimped onto fiberglass rod, material of housing and sheds manufacture of high-temperature Vulcanized Silicone Rubber, and the insulator moulded by one piece injection molding. It has good sealing performance and good performance of tracking and erosion resistance.
All ferrous parts processed by hot dip galvanized, its zinc coating more than 86u, it has good corrosion resistance.
Suitable for 36kV power distribution systems
Reliable overload and short circuit protection
High mechanical strength and stable performance
Excellent insulation and weather resistance
Hot dip galvanized metal fittings
Easy installation and maintenance
Suitable for outdoor utility applications
Long service life in harsh environment

Overhead power distribution lines
Electrical substations
Utility pole protection systems
Rural and urban electrical networks
High voltage transmission projects
Outdoor electrical protection systems
• Fix the 36kV drop out fuse cutout onto a pole structure or mounting bracket.
• Attach the incoming conductor to the top contact terminal.
• Connect the outgoing circuit or transformer to the lower terminal.
• Install a suitable fuse element according to load requirements.
• Use an insulated operating rod for switching and replacement.
| Product Name | 36kV Drop Out Fuse Cutout |
| Rated Voltage | 36kV |
| Material | Porcelain / Polymer + Galvanized Steel |
| Application | Power Distribution System |
| Installation | Outdoor Utility Pole |
| OEM Service | Available |
| Rated voltage(KV) | Rated current(A) | Rated interrupting current(KA) | Lightning impulse withstand voltage to ground (BIL KV) | Minimum power frequency withstand dry voltage to ground (KV) | Minimum creepage distance(mm) |
| 11-15 | 100/200 | 12 | 110 | 42 | 220 |
| 11-15 | 100/200 | 12 | 125 | 50 | 320 |
| 24-27 | 100/200 | 12 | 150 | 65 | 470 |
| 33-38 | 100/200 | 8 | 170 | 70 | 660 |
| 33-38 | 100/200 | 8 | 170 | 70 | 720 |
| 33-38 | 100/200 | 8 | 170 | 70 | 900 |
Carefully selected insulating components
Stable interrupting and mechanical performance
Resistance to environmental aging and corrosion
Routine inspection during production process
Final performance verification before shipment
Q1: What is a drop out fuse cutout used for?
A1: A drop out fuse cutout is used to protect overhead power distribution systems from overload and short circuit faults.
Q2: Is the product suitable for outdoor use?
A2: Yes. The fuse cutout is designed for outdoor electrical utility applications and provides excellent weather resistance.
Q3: What materials are used in the fuse cutout?
A3: The product is typically manufactured with porcelain or polymer insulation components and hot dip galvanized steel hardware.
Q4: Do you support customized specifications?
A4: Yes. Reacon supports OEM manufacturing and customized solutions according to customer requirements.