1.The altitude above sea level:2000m
2.The ambient air temperature:-40~40'℃ wind speed does not exceed 32m/s.
3.The earthquake intensity does not exceed 8 degrees.
4.The working situation is without frequent violent vibration.
5.The installation site of ordinary type isolator should be kept away from gas,smoke chemical deposition,salt-spray fog, dust and other explosive and corrosive maters that affect seriously insulation and conduction capability of the isolator.
6.Pollution-proof type isolator is applies to severe filthy conduction area, however,it shouldn't be any explosive matters and matters causing fire.
Technical Specification:
No. | Item | Unit | Data | ||
1 | Rated voltage | kV | 12,36 | ||
2 | Rated current | A | 630 | ||
3 | Rated power frequency | Hz | 50/60 | ||
4 | Rated peak withstand current | kA | 60,63 | ||
5 | Rated short-time withstand current | kA | 20,25 | ||
6 | Rated short-time withstand current duration | S | 4 | ||
7 | Main loop resistance | μ Ω | 12kV≤90 | 36kV≤100 | |
8 | 1min.PF withstand voltage(dry) | Phase to phase/ earth across open contacts | kV | 42/48 30 75/85 | 95/115 85 185/215 |
9 | 1min.PF withstand voltage(wet) | ||||
10 | Lightning impulse withstand voltage | ||||
11 | Mechanical life | Times | 200 |