| Availability: | |
|---|---|
| Quantity: | |
The 24kV 630A Outdoor High Voltage Isolator Switch is engineered for reliable power disconnection and switching control in medium-voltage distribution systems. With its durable insulated structure, corrosion-resistant steel components, and high mechanical endurance, this outdoor high voltage isolator switch ensures safe and stable operation under harsh environmental conditions including rain, salt fog, dust, and extreme temperatures. Designed for power substations, overhead lines, industrial distribution networks, and utility infrastructure, this 24kV 630A isolator switch provides clear visible isolation to protect workers and equipment during maintenance or emergency isolation operations.
• Efficient Mechanical Operation
Ensures smooth switching with low operating torque.
• High Dielectric Strength
Provides stable insulation performance under 24kV working voltage.
• Weatherproof Outdoor Construction
Resistant to UV, corrosion, rain, and environmental stress.
• Visible Break Guarantee
Provides clear isolation indication for safety compliance.
• Long Service Life
Expected operational lifespan of 25–30 years.
1.The altitude above sea level:2000m
2.The ambient air temperature:-40~40'℃ wind speed does not exceed 32m/s.
3.The earthquake intensity does not exceed 8 degrees.
4.The working situation is without frequent violent vibration.
5.The installation site of ordinary type isolator should be kept away from gas,smoke chemical deposition,salt-spray fog, dust and other explosive and corrosive maters that affect seriously insulation and conduction capability of the isolator.
6.Pollution-proof type isolator is applies to severe filthy conduction area, however,it shouldn't be any explosive matters and matters causing fire.

Technical Specification:
| No. | Item | Unit | Data | ||
| 1 | Rated voltage | kV | 12,36 | ||
| 2 | Rated current | A | 630 | ||
| 3 | Rated power frequency | Hz | 50/60 | ||
| 4 | Rated peak withstand current | kA | 60,63 | ||
| 5 | Rated short-time withstand current | kA | 20,25 | ||
| 6 | Rated short-time withstand current duration | S | 4 | ||
| 7 | Main loop resistance | μ Ω | 12kV≤90 | 36kV≤100 | |
| 8 | 1min.PF withstand voltage(dry) | Phase to phase/ earth across open contacts | kV | 42/48 30 75/85 | 95/115 85 185/215 |
| 9 | 1min.PF withstand voltage(wet) | ||||
| 10 | Lightning impulse withstand voltage | ||||
| 11 | Mechanical life | Times | 200 | ||
Every 24kV 630A Outdoor High Voltage Isolator Switch undergoes strict production inspection, including dielectric testing, mechanical endurance testing, weather resistance evaluation, and load simulation testing. The product meets IEC, GB, and ANSI applicable standards and includes full traceability manufacturing records with optional third-party test reports.
Q1: Can the isolator switch operate under full load?
A1: No, the 24kV 630A isolator switch is designed for no-load switching operations.
Q2: What is the typical installation height?
A2: Usually mounted 4–10 meters above ground depending on site requirements.
Q3: Does it require regular maintenance?
A3: Yes, periodic lubrication and inspection are recommended every 12–24 months.